1. INSPECT THERMOSTAT
(a) Inspect the thermostat.
HINT: The valve opening temperature is inscribed on the thermostat.
(b) Immerse the thermostat in water and gradually heat the water.
(c) Check the valve opening temperature.
Valve opening temperature: 80 to 84°C (176 to 183°F) If the valve opening temperature is not as specified, replace the thermostat.
(d) Check the valve lift.
Valve lift: 7.7 mm (0.303 in.) or more at 95°C (203°F) If the valve lift is not as specified, replace the thermostat.
(e) Check that the valve is fully closed when the thermostat is at low temperatures (below 40°C (104°F)).
If it is not fully closed, replace the thermostat.
Gateway ECU Communication Stop Mode
DESCRIPTION
Detection Item
Symptom
Trouble Area
Gateway ECU
Communication Stop
Mode
"Gateway" is not displayed on the "Communication
Bus Check" screen of the intelligent tester
Applies to "Gateway ECU Communication ...
Rear Door ECU LH Communication Stop
DTC B1217 Rear Door ECU LH Communication Stop
DESCRIPTION
DTC B1217 is output when communication between the power slide door ECU LH
and the multiplex
network gateway ECU stops for more than 10 seconds.
DTC No.
DTC Detection Condition
Trouble Area
B1217
...
Installation
HINT:
Use the same procedures for the RH side and LH side.
The procedures listed below are for the LH side.
1. INSTALL CURTAIN SHIELD AIRBAG ASSEMBLY LH
Install the curtain shield airbag assembly LH with
the 13 bolts in the order shown in the illustration.
Torque: 14 N*m ...